The British standards associated with sprinkler systems are as follows.
BS 9251 is the main British Standard covering fire sprinklers in this country. BS 9251 gives guidance for the design, installation, components, water supplies and backflow protection, commissioning, maintenance and testing of fire sprinkler systems installed for life safety purposes with additional benefits for property protection in residential and domestic occupancies.
Sprinkler systems are the most effective way to ensure that fires are suppressed or even extinguished before the fire rescue service can attend the site. Sprinkler systems save lives and can reduce injuries, the additional benefit of protecting firefighters who attend incidents and contribute to reducing the amount of damage to both property and the environment from fire. BS 9251: 2014, British Standard for Fire sprinkler Systems for Domestic and Residential Occupancies. Specifically for domestic and residential fire sprinkler installations. This standard sets the minimum requirements for the design, installation, and commission of a fire sprinkler system.
Specific requirements for a sprinkler systems are shown below:
- Minimum flow rates: 60 litres per minute (lpm) through a single nozzle or 42lpm for multiple nozzles.
- Minimum design: 2 nozzles for domestic and 4 nozzles for residential properties.
- Minimum duration: 10 minutes for domestic properties, 30 minutes for residential properties.
- Minimum nozzle spacings: no more than 2m from any wall or corner, no closer apart than 4m.
The National Fire Sprinkler Network Report 2017 stated the following, reducing average property loss by up to 70% . In the UK there has never been a fire death in a building with a fully maintained sprinkler system. Fires are extinguished or controlled in 99% of sprinkler protected properties.
Weekly Testing & Servicing of Fire Sprinkler Systems
- Testing alarms, Pump/engine test.
- Test air compressors if installed, Check isolating valve positions, Heating systems/frost protection Monthly: Battery level checks, Water Storage tank security
Routine Servicing of Fire Sprinkler Systems
- Quarterly: Review of hazard, Inspection of pipework/supports, Water supply flow tests, Exercise stop valves, Test flow switches.
- Six Monthly: Alternate pipe system – change over from air to water/ water to air, Check electrical signal to Fire brigade Annually: Pump service, Check tank ball float valves, Engine service, Valve service/inspection.
- 3 Yearly: Inspect tanks, All valves & non return valves, Inspection, service and overhaul as necessary.
- Other Intervals: Tank drain down & clean – 10 yearly, Sprinkler head performance testing to suit rules.
In the UK residential and domestic fire sprinklers need to be serviced at least every 12 months. This is a legal requirement, so you do need to ensure that you get these systems serviced if they’re in your premises and it’s your responsibility to do so. The legal requirement is set out by the British Standard BS 9251:2014 which covers the regulations for all types of fire sprinkler systems.
Companies Fined For Safety Failures At Apartments Fire
A judge has credited pure luck and the swift response of firefighters for preventing a potentially fatal disaster at a block of flats plagued by fire safety deficiencies. In February 2021, a fire at Tower Chambers in Hartlepool necessitated the rescue of seventeen individuals.
Registered Duty Holders & Fire Risk Assessments
Over 13,000 dutyholders have initiated or completed their registration applications for the new regulatory framework established by the Building Safety Regulator (BSR), which became effective on October 1st. Principal Accountable Persons (PAPs) were granted until the end of September to register all high-rise residential buildings that are at least 18 meters or seven stories tall, as mandated by the Building Safety Act of 2022.
Electric Vehicle Fleet Fire Risks In The Spotlight
Residents have been voicing opposition to the construction of an underground electric bus garage beneath the planned building of numerous new residential apartments. Their concerns revolve around the potential for battery fires to create a destructive "volcano" and threaten the neighbourhood.
Externally Monitored to Ensure that we meet a High Standard of Service.
As members of the SSAIB (Security Systems and Alarms Inspection Board), We maintain service records and monitor our success. The SSAIB, is a leading certification body for organisations providing security systems and services, fire detection alarm systems, and monitoring services. So, you can be confident that we strive to provide our clients with a reliable and professional level of service.