FIRE SPRINKLER SYSTEMS
Commercial Fire Sprinkler Systems
The British standards associated with sprinkler systems are as follows.
BS 9251 is the main British Standard covering fire sprinklers in this country. BS 9251 gives guidance for the design, installation, components, water supplies and backflow protection, commissioning, maintenance and testing of fire sprinkler systems installed for life safety purposes with additional benefits for property protection in residential and domestic occupancies.
Sprinkler systems are the most effective way to ensure that fires are suppressed or even extinguished before the fire rescue service can attend the site. Sprinkler systems save lives and can reduce injuries, the additional benefit of protecting firefighters who attend incidents and contribute to reducing the amount of damage to both property and the environment from fire. BS 9251: 2014, British Standard for Fire sprinkler Systems for Domestic and Residential Occupancies. Specifically for domestic and residential fire sprinkler installations. This standard sets the minimum requirements for the design, installation, and commission of a fire sprinkler system.
Specific requirements for a sprinkler systems are shown below:
- Minimum flow rates: 60 litres per minute (lpm) through a single nozzle or 42lpm for multiple nozzles.
- Minimum design: 2 nozzles for domestic and 4 nozzles for residential properties.
- Minimum duration: 10 minutes for domestic properties, 30 minutes for residential properties.
- Minimum nozzle spacings: no more than 2m from any wall or corner, no closer apart than 4m.
The National Fire Sprinkler Network Report 2017 stated the following, reducing average property loss by up to 70% . In the UK there has never been a fire death in a building with a fully maintained sprinkler system. Fires are extinguished or controlled in 99% of sprinkler protected properties.
Weekly Testing & Servicing of Fire Sprinkler Systems
- Testing alarms, Pump/engine test.
- Test air compressors if installed, Check isolating valve positions, Heating systems/frost protection Monthly: Battery level checks, Water Storage tank security
Routine Servicing of Fire Sprinkler Systems
- Quarterly: Review of hazard, Inspection of pipework/supports, Water supply flow tests, Exercise stop valves, Test flow switches.
- Six Monthly: Alternate pipe system – change over from air to water/ water to air, Check electrical signal to Fire brigade Annually: Pump service, Check tank ball float valves, Engine service, Valve service/inspection.
- 3 Yearly: Inspect tanks, All valves & non return valves, Inspection, service and overhaul as necessary.
- Other Intervals: Tank drain down & clean – 10 yearly, Sprinkler head performance testing to suit rules.
In the UK residential and domestic fire sprinklers need to be serviced at least every 12 months. This is a legal requirement, so you do need to ensure that you get these systems serviced if they’re in your premises and it’s your responsibility to do so. The legal requirement is set out by the British Standard BS 9251:2014 which covers the regulations for all types of fire sprinkler systems.
Frequently Asked Questions About Commercial Fire Sprinkler Systems
Advice When Choosing, Installing and Maintaining Commercial Fire Sprinkler Systems
Bonus Tip: Keep an up-to-date sprinkler system layout and asset register alongside your maintenance records. Include the locations of control valves, pumps, water storage tanks, sprinkler zones and relevant test points. This helps maintenance teams locate equipment, supports routine inspections and makes it easier to assess the impact of future building alterations.
Fire Safety First & The Importance Of Fire Warden & Fire Extinguisher Training
Discover why fire warden and fire extinguisher training is essential for workplace fire safety. Learn how SS Systems helps businesses improve fire awareness, prevent risks and prepare employees for emergencies.
Considerations Before Selecting a Fire Alarm System for a Commercial Property
Choosing a fire alarm system for a commercial property? Explore key considerations including fire risk, system type, building requirements, compliance, accessibility and ongoing maintenance.
One Engineer With Multiple Disciplines & A More Joined-Up Approach
Modern buildings increasingly rely on multiple fire, life-safety and security systems working together. From fire alarms and emergency systems to CCTV, access control and intruder detection, ensuring these technologies operate effectively requires more than simply understanding each system in isolation. A multi-disciplined fire and security engineer brings knowledge and skills across both fire and security systems, providing a more coordinated approach to installation, integration, servicing and ongoing support.
OUR PARTNERS
SS Systems partner with leading UK based manufacturers to ensure that the fire detection and alarm systems we provide are at the forefront of current technology, along with being the most reliable our industry has to offer.
Externally Monitored to Ensure that we meet a High Standard of Service.
As members of the SSAIB (Security Systems and Alarms Inspection Board), We maintain service records and monitor our success. The SSAIB, is a leading certification body for organisations providing security systems and services, fire detection alarm systems, and monitoring services. So, you can be confident that we strive to provide our clients with a reliable and professional level of service.