Commercial Fire Sprinkler Systems

The British standards associated with sprinkler systems are as follows.

BS 9251 is the main British Standard covering fire sprinklers in this country. BS 9251 gives guidance for the design, installation, components, water supplies and backflow protection, commissioning, maintenance and testing of fire sprinkler systems installed for life safety purposes with additional benefits for property protection in residential and domestic occupancies.

Sprinkler systems are the most effective way to ensure that fires are suppressed or even extinguished before the fire rescue service can attend the site. Sprinkler systems save lives and can reduce injuries, the additional benefit of protecting firefighters who attend incidents and contribute to reducing the amount of damage to both property and the environment from fire. BS 9251: 2014, British Standard for Fire sprinkler Systems for Domestic and Residential Occupancies. Specifically for domestic and residential fire sprinkler installations. This standard sets the minimum requirements for the design, installation, and commission of a fire sprinkler system.

Specific requirements for a sprinkler systems are shown below:

  • Minimum flow rates: 60 litres per minute (lpm) through a single nozzle or 42lpm for multiple nozzles.
  • Minimum design: 2 nozzles for domestic and 4 nozzles for residential properties.
  • Minimum duration: 10 minutes for domestic properties, 30 minutes for residential properties.
  • Minimum nozzle spacings: no more than 2m from any wall or corner, no closer apart than 4m.

The National Fire Sprinkler Network Report 2017 stated the following, reducing average property loss by up to 70% . In the UK there has never been a fire death in a building with a fully maintained sprinkler system. Fires are extinguished or controlled in 99% of sprinkler protected properties.

Weekly Testing & Servicing of Fire Sprinkler Systems

  • Testing alarms, Pump/engine test.
  • Test air compressors if installed, Check isolating valve positions, Heating systems/frost protection Monthly: Battery level checks, Water Storage tank security

Routine Servicing of Fire Sprinkler Systems

  • Quarterly: Review of hazard, Inspection of pipework/supports, Water supply flow tests, Exercise stop valves, Test flow switches.
  • Six Monthly: Alternate pipe system – change over from air to water/ water to air, Check electrical signal to Fire brigade Annually: Pump service, Check tank ball float valves, Engine service, Valve service/inspection.
  • 3 Yearly: Inspect tanks, All valves & non return valves, Inspection, service and overhaul as necessary.
  • Other Intervals: Tank drain down & clean – 10 yearly, Sprinkler head performance testing to suit rules.

In the UK residential and domestic fire sprinklers need to be serviced at least every 12 months. This is a legal requirement, so you do need to ensure that you get these systems serviced if they’re in your premises and it’s your responsibility to do so. The legal requirement is set out by the British Standard BS 9251:2014 which covers the regulations for all types of fire sprinkler systems.

Enquiry

Council CCTV Offers Limited Public Protection

By |December 16th, 2024|Categories: News|Tags: , , , , , |

Following on from a recent news item by SS Systems on council CCTV systems, another local authority has been in the news regarding the effectiveness of closed circuit television systems. Eastleigh Council has recently reviewed its aging CCTV system amid cost and effectiveness concerns. Eastleigh Borough Council's public realm Closed Circuit Television (CCTV) system was viewed to be no longer meeting modern standards, offering "limited public protection" and being unsustainable to operate, according to a report presented to local authority councillors. The report concluded that the current system requires decommissioning due to its outdated technology and high operating costs.

Restaurant Owner Fined For Serious Fire Safety Violations

By |December 9th, 2024|Categories: News|Tags: , , , , , |

A restaurant owner on Wellingborough Road, Northampton, has been fined after an inspection by Northamptonshire Fire and Rescue Service uncovered severe breaches of the Regulatory Reform (Fire Safety) Order 2005, putting employees at significant risk.

Tyre Fires See Firefighters Called Out At Two Separate Businesses

By |December 2nd, 2024|Categories: News|Tags: , , , , , |

Norfolk Fire Service responded to a significant fire at a discount tyre company in Saddlebow, near King's Lynn, involving tyres and industrial equipment. Fire crews from King’s Lynn, Fakenham, Terrington, Massingham, Heacham, and Downham Market were dispatched to the scene on High Road, utilising a thermal imaging camera to identify hot spots. Residents were advised to keep doors and windows closed due to the smoke.

Externally Monitored to Ensure that we meet a High Standard of Service.

As members of the SSAIB (Security Systems and Alarms Inspection Board), We maintain service records and monitor our success. The SSAIB, is a leading certification body for organisations providing security systems and services, fire detection alarm systems, and monitoring services. So, you can be confident that we strive to provide our clients with a reliable and professional level of service.

Go to Top