Commercial Fire Sprinkler Systems2025-12-08T13:24:53+00:00

FIRE SPRINKLER SYSTEMS

Commercial Fire Sprinkler Systems

The British standards associated with sprinkler systems are as follows.

BS 9251 is the main British Standard covering fire sprinklers in this country. BS 9251 gives guidance for the design, installation, components, water supplies and backflow protection, commissioning, maintenance and testing of fire sprinkler systems installed for life safety purposes with additional benefits for property protection in residential and domestic occupancies.

Sprinkler systems are the most effective way to ensure that fires are suppressed or even extinguished before the fire rescue service can attend the site. Sprinkler systems save lives and can reduce injuries, the additional benefit of protecting firefighters who attend incidents and contribute to reducing the amount of damage to both property and the environment from fire. BS 9251: 2014, British Standard for Fire sprinkler Systems for Domestic and Residential Occupancies. Specifically for domestic and residential fire sprinkler installations. This standard sets the minimum requirements for the design, installation, and commission of a fire sprinkler system.

Specific requirements for a sprinkler systems are shown below:

  • Minimum flow rates: 60 litres per minute (lpm) through a single nozzle or 42lpm for multiple nozzles.
  • Minimum design: 2 nozzles for domestic and 4 nozzles for residential properties.
  • Minimum duration: 10 minutes for domestic properties, 30 minutes for residential properties.
  • Minimum nozzle spacings: no more than 2m from any wall or corner, no closer apart than 4m.

The National Fire Sprinkler Network Report 2017 stated the following, reducing average property loss by up to 70% . In the UK there has never been a fire death in a building with a fully maintained sprinkler system. Fires are extinguished or controlled in 99% of sprinkler protected properties.

Weekly Testing & Servicing of Fire Sprinkler Systems

  • Testing alarms, Pump/engine test.
  • Test air compressors if installed, Check isolating valve positions, Heating systems/frost protection Monthly: Battery level checks, Water Storage tank security

Routine Servicing of Fire Sprinkler Systems

  • Quarterly: Review of hazard, Inspection of pipework/supports, Water supply flow tests, Exercise stop valves, Test flow switches.
  • Six Monthly: Alternate pipe system – change over from air to water/ water to air, Check electrical signal to Fire brigade Annually: Pump service, Check tank ball float valves, Engine service, Valve service/inspection.
  • 3 Yearly: Inspect tanks, All valves & non return valves, Inspection, service and overhaul as necessary.
  • Other Intervals: Tank drain down & clean – 10 yearly, Sprinkler head performance testing to suit rules.

In the UK residential and domestic fire sprinklers need to be serviced at least every 12 months. This is a legal requirement, so you do need to ensure that you get these systems serviced if they’re in your premises and it’s your responsibility to do so. The legal requirement is set out by the British Standard BS 9251:2014 which covers the regulations for all types of fire sprinkler systems.

Enquiry

Congratulations To Amanda Sampson For 15 Years At SS Systems

By |March 27th, 2025|Categories: News|Tags: , , , , |

On behalf of everyone at SS Systems I would like to share a huge thank you to Amanda for 15 years of excellent service. Amanda is a key member of the SS Systems family, providing great customer service to our clients and helping to create a friendly and positive environment within the office. Amanda finds time to support both internal and external colleagues with a friendly professional approach.

Government Publishes Research on E-Bike and E-Scooter Battery Safety

By |March 24th, 2025|Categories: News|Tags: , , , , |

The UK government has released the results of an independent study on the safety of lithium-ion batteries used in e-bikes, e-scooters, chargers, and conversion kits. The research, commissioned by the Office for Product Safety and Standards (OPSS), aims to deepen the government's understanding of the risks posed by unsafe batteries, particularly in light of a surge in fire incidents linked to these products.

Government To Investigate Seven Organisations Over Grenfell Tower Disaster

By |March 17th, 2025|Categories: News|Tags: , , , , |

The UK government has announced that seven organisations will be investigated in relation to the Grenfell Tower disaster, with all recommendations from the public inquiry set to be implemented. As part of the changes, manufacturing companies under scrutiny could be barred from bidding for public contracts, and two existing bodies will be merged to create a single building safety regulator.

Externally Monitored to Ensure that we meet a High Standard of Service.

As members of the SSAIB (Security Systems and Alarms Inspection Board), We maintain service records and monitor our success. The SSAIB, is a leading certification body for organisations providing security systems and services, fire detection alarm systems, and monitoring services. So, you can be confident that we strive to provide our clients with a reliable and professional level of service.